Protection Coordination & SelectivityIEC 60947-2
Verify upstream/downstream circuit breaker discrimination, current & time grading, energy selectivity tables, and cable thermal withstand.
Upstream Protective Device
Source SideOverload Ir400 A
100% of InDelay tr12 s
Short-Time Isd2400 A
6x IrDelay tsd0.2 s
Instantaneous Ii4000 A
10x InManufacturer
Downstream Protective Device
Load Side5–10x In (Standard)
Prospective Fault Level & Feeder Cable
kA
FULL SELECTIVITY
Energy Selectivity Table Applied
Total Discrimination Guaranteed
Fully selective up to 25.0 kA (exceeds prospective fault level 25.0 kA).
IEC 60947-2 Coordination Verification Stages
Step-by-step evaluation of thermal grading, time delays, energy let-through, and cable protection
1. Overload Current Grading (Ir,up ≥ 1.6 x Ir,down)Upstream Ir (400A) vs Downstream Ir (63A). Ratio: 6.35x
PASSED
2. Short-Time Discrimination Margin (at 10x In)Evaluated time separation between trip curves: 291.75s (Margin required ≥ 0.25s)
PASSED
3. Energy Selectivity (I²t) / Tested Manufacturer TablesTested combination certified by Schneider (ABB DOC / Schneider ECODIAL tables applied).
CERTIFIED
4. Cable Short-Circuit Withstand (k²S² ≥ I²t)IEC 60364-4-43 thermal damage check on 16 mm² feeder under 25 kA prospective fault.
PASSED
ProCal : Low Voltage Electrical Design, Solved
Avoid Total Blackouts with Automated Substation Selectivity
In ProCal, breaker settings across Main MV/LV Transformers, Sub-Distribution Panels (SMDB), and Floor Distribution Boards (DB) are continuously audited for 100% selective discrimination and cascading back-up protection.
Multi-Floor RisersIEC 61439-2 automated diversity across towers
Dynamic SLD GenerationInteractive Single Line Diagram with live breaker sync
1-Click ExportCompliant PDF & Excel calculation schedules