IEC Cable Sizer & Breaker Selector
Free online electrical calculator for low-voltage power cables. Automatically sizes cross-section, calculates derating factors (kt, kg), coordinates overcurrent protection (Ib ≤ In ≤ Iz), and verifies voltage drop (ΔV).
1. Electrical Load & System
Specify the design load and electrical supply parameters
2. Route Length & Voltage Drop Limit
IEC 60364-5-52 §525 limits: 3% for lighting, 5% for other uses
3. Cable Specification & Installation
Installation method and ambient correction factors per IEC 60364-5-52
16 mm²
Copper Conductor, XLPE Insulation (Method C)
Need to size an entire switchboard or multi-floor riser?
In ProCal, your cables, breakers, transformer fault levels, and diversity factors are automatically synchronized across multi-floor risers and exportable Single Line Diagrams.
How IEC 60364-5-52 Low-Voltage Cable Sizing Works
Cable sizing according to international standard IEC 60364-5-52 requires verifying two core criteria: thermal ampacity under installation conditions, and maximum permissible voltage drop across the run.
1. Overload Protection (IEC 60364-4-43)
The continuous current rating of the protective device (In) and the cable's derated current-carrying capacity (Iz) must satisfy the fundamental coordination chain:
Where Ib is the circuit design current, In is the nominal rating of the circuit breaker or fuse, and Iz = I_base × kt × kg is the effective current-carrying capacity under ambient and grouping derating.
2. Voltage Drop Compliance (Clause 525)
Under normal operating conditions, the voltage drop between the origin of the installation and the terminal equipment should not exceed standard limits:
- 3% for lighting installations
- 5% for general power and heating
For long runs, the cable cross-section must often be upsized beyond the thermal Iz requirement to prevent equipment malfunction and excessive line losses.