Motor & HVAC Protection SizerIEC 60947-4-1
Full Load Current (FLC), starting inrush spikes, MPCB / overload dial settings, AC-3 contactors, and motor feeder cable run.
Motor Nameplate Specifications
Mechanical shaft power, voltage supply, and efficiency rating
kW
Equivalent: 49.6 HPEffective η: 93.5%
0.86
0.70 (Small Induction)0.86 (Typical 30kW+)0.95 (High PF)
40 meters
Length (m)
Conductor
Insulation
Max Running ΔV3%
Max Starting ΔV15%
Full Load Current66.4 Acos φ = 0.86
Starting Inrush431.7 A6.5x FLC peak
Input Power39.6 kW46.0 kVA Apparent
Contactor AC-380 AIEC 60947-4-1
Motor Protection Switchgear (IEC 60947-4-1)
MPCB thermal setting dial, magnetic trip threshold, and contactor ratings
Type 2 Coordinated
MPCB Thermal Overload (Ir)
1.0 x FLC
66.4 Adial setting
Recommended MPCB thermal range: 65 A – 80 A. Adjust dial to exactly 66.4 A.
Magnetic Short-Circuit (Im)
Instantaneous
863 Atrip threshold
Sized above starting inrush current (431.7 A) to prevent nuisance tripping during motor acceleration.
Contactor Configuration (AC-3 Utilization Category)IEC 60947-4-1
Main Line Contactor (KM1)Rated continuous AC-3 breaking capacity ≥ 66.4 A
80 A AC-3Motor Feeder Cable Sizing & Starting Drop Verification
Continuous ampacity (Iz ≥ In) and starting voltage drop (≤ 15%) per IEC 60364-5-52
Running Sizing Governs
Selected Feeder Cable16 mm²Iz = 96.0 A
Running ΔVPASSED
1.41%5.7 V (Limit: 3%)Starting ΔVPASSED
4.19%16.7 V (Limit: 15%)ProCal : Low Voltage Electrical Design, Solved
Integrate Motor Loads Directly into Building Risers & SLDs
In ProCal, mechanical equipment schedules (chillers, AHUs, pumps, lifts) automatically sync to their respective MCC panels, calculate starting inrush on standby generators, and reflect on interactive Single Line Diagrams.
Multi-Floor RisersIEC 61439-2 automated diversity across towers
Dynamic SLD GenerationInteractive Single Line Diagram with live breaker sync
1-Click ExportCompliant PDF & Excel calculation schedules