Short-Circuit & Breaker Breaking Capacity Calculator
Calculate symmetrical short-circuit current (Ik''), peak making current (Ip), and determine the minimum required circuit breaker breaking capacity (Icu / Ics) at transformer terminals and downstream sub-distribution boards.
1. Distribution Transformer
Select rating and impedance specifications
2. Downstream Feeder Cable (Optional)
Calculates fault current attenuation at sub-distribution board
All main incomer and bus-tie breakers on the Low-Voltage Main Switchboard (MDB) must be rated for at least 36 kA breaking capacity.
Coordinate Switchgear Fault Levels & Selectivity in ProCal
ProCal propagates busbar short-circuit levels down multi-tier risers, verifies breaker Icu ratings and cascading, and generates synchronized Single Line Diagrams.
How IEC 60909 Short-Circuit Currents Are Calculated
Under IEC 60909, prospective short-circuit currents are determined using the equivalent voltage source method at the fault location:
1. Transformer Impedance (Zt)
Where uk% is the percentage short-circuit impedance voltage, Un is secondary nominal voltage, and Sr is transformer rated apparent power.
2. Symmetrical Fault Current (Ik'')
Where c_max = 1.05 (for low-voltage systems) accounts for utility voltage fluctuations.