Short-Circuit & Breaker Breaking Capacity Calculator

Calculate symmetrical short-circuit current (Ik''), peak making current (Ip), and determine the minimum required circuit breaker breaking capacity (Icu / Ics) at transformer terminals and downstream sub-distribution boards.

1. Distribution Transformer

Select rating and impedance specifications

6%

2. Downstream Feeder Cable (Optional)

Calculates fault current attenuation at sub-distribution board

Fault Analysis (IEC 60909)
3-Phase Symmetrical Fault Current (Ik'') at Transformer:
25.26 kA(17.5 MVA)
Required Switchboard Breaker Icu: ≥ 36 kA

All main incomer and bus-tie breakers on the Low-Voltage Main Switchboard (MDB) must be rated for at least 36 kA breaking capacity.

Peak Making Current (Ip)57.67 kAMechanical busbar stress
Phase-to-Phase (Ik2)21.87 kA0.866 × Ik''
Phase-to-Neutral (Ik1)25.26 kASequence impedance ratio
Transformer Impedance (Zt)9.60 mΩAt 400V secondary
ProCal : Low Voltage Electrical Design, Solved

Coordinate Switchgear Fault Levels & Selectivity in ProCal

ProCal propagates busbar short-circuit levels down multi-tier risers, verifies breaker Icu ratings and cascading, and generates synchronized Single Line Diagrams.

Multi-Floor RisersIEC 61439-2 automated diversity across towers
Dynamic SLD GenerationInteractive Single Line Diagram with live breaker sync
1-Click ExportCompliant PDF & Excel calculation schedules

How IEC 60909 Short-Circuit Currents Are Calculated

Under IEC 60909, prospective short-circuit currents are determined using the equivalent voltage source method at the fault location:

1. Transformer Impedance (Zt)

Z_t = (u_k% / 100) × (U_n² / S_r)

Where uk% is the percentage short-circuit impedance voltage, Un is secondary nominal voltage, and Sr is transformer rated apparent power.

2. Symmetrical Fault Current (Ik'')

I_k'' = (c_max × U_n) / (√3 × Z_total)

Where c_max = 1.05 (for low-voltage systems) accounts for utility voltage fluctuations.