IEC 60364-5-52 §525 Voltage Drop Matrix

Maximum Cable Run Length Calculator

Find the maximum permissible distance for every cable cross-section before exceeding voltage drop limits, or enter your target run length to identify the minimum compliant cable size.

Circuit Load & Specifications

Define load current, voltage, and permissible drop

Design Current (Ib):50.9 A
50 m
Full Riser Distribution

Multi-Floor Riser Voltage Drop

ProCal calculates cumulative voltage drop across building risers, tap-off boxes, and apartment sub-panels with diversity factors.

Maximum Permissible Length Matrix

Distance limit before exceeding 4% (16.0 V) voltage drop at 50.9 A

For 50 meters, minimum size is: 6 mm²
ΔV = 3.53%
Size (mm²)Base Iz (A)Max Run (m)Drop at 50mStatus
1.5 mm²22 A14 m13.94% (55.8 V)Iz < Ib
2.5 mm²30 A23 m8.41% (33.7 V)Iz < Ib
4 mm²40 A37 m5.28% (21.1 V)Iz < Ib
6 mm²52 A56 m3.53% (14.1 V)★ Recommended
10 mm²71 A95 m2.10% (8.4 V)Compliant
16 mm²96 A149 m1.34% (5.4 V)Compliant
25 mm²119 A232 m0.86% (3.5 V)Compliant
35 mm²147 A314 m0.63% (2.5 V)Compliant
50 mm²179 A416 m0.48% (1.9 V)Compliant
70 mm²229 A579 m0.34% (1.4 V)Compliant
95 mm²278 A769 m0.26% (1.0 V)Compliant
120 mm²322 A930 m0.21% (0.8 V)Compliant
150 mm²371 A1111 m0.18% (0.7 V)Compliant
185 mm²424 A1333 m0.15% (0.6 V)Compliant
240 mm²500 A1600 m0.12% (0.5 V)Compliant
300 mm²576 A1904 m0.11% (0.4 V)Compliant
ProCal : Low Voltage Electrical Design, Solved

Manage Building-Wide Voltage Drop Distribution in ProCal

Eliminate cable sizing guesswork. ProCal balances voltage drop budgets across multi-tier distribution: from MV/LV transformer to main switchboard, sub-panels, and final circuit outlets.

Multi-Floor RisersIEC 61439-2 automated diversity across towers
Dynamic SLD GenerationInteractive Single Line Diagram with live breaker sync
1-Click ExportCompliant PDF & Excel calculation schedules