IEC 60364-5-52 §525 Voltage Drop Matrix
Maximum Cable Run Length Calculator
Find the maximum permissible distance for every cable cross-section before exceeding voltage drop limits, or enter your target run length to identify the minimum compliant cable size.
Circuit Load & Specifications
Define load current, voltage, and permissible drop
Design Current (Ib):50.9 A
50 m
Maximum Permissible Length Matrix
Distance limit before exceeding 4% (16.0 V) voltage drop at 50.9 A
For 50 meters, minimum size is: 6 mm²
ΔV = 3.53%| Size (mm²) | Base Iz (A) | Max Run (m) | Drop at 50m | Status |
|---|---|---|---|---|
| 1.5 mm² | 22 A | 14 m | 13.94% (55.8 V) | Iz < Ib |
| 2.5 mm² | 30 A | 23 m | 8.41% (33.7 V) | Iz < Ib |
| 4 mm² | 40 A | 37 m | 5.28% (21.1 V) | Iz < Ib |
| 6 mm² | 52 A | 56 m | 3.53% (14.1 V) | ★ Recommended |
| 10 mm² | 71 A | 95 m | 2.10% (8.4 V) | Compliant |
| 16 mm² | 96 A | 149 m | 1.34% (5.4 V) | Compliant |
| 25 mm² | 119 A | 232 m | 0.86% (3.5 V) | Compliant |
| 35 mm² | 147 A | 314 m | 0.63% (2.5 V) | Compliant |
| 50 mm² | 179 A | 416 m | 0.48% (1.9 V) | Compliant |
| 70 mm² | 229 A | 579 m | 0.34% (1.4 V) | Compliant |
| 95 mm² | 278 A | 769 m | 0.26% (1.0 V) | Compliant |
| 120 mm² | 322 A | 930 m | 0.21% (0.8 V) | Compliant |
| 150 mm² | 371 A | 1111 m | 0.18% (0.7 V) | Compliant |
| 185 mm² | 424 A | 1333 m | 0.15% (0.6 V) | Compliant |
| 240 mm² | 500 A | 1600 m | 0.12% (0.5 V) | Compliant |
| 300 mm² | 576 A | 1904 m | 0.11% (0.4 V) | Compliant |
ProCal : Low Voltage Electrical Design, Solved
Manage Building-Wide Voltage Drop Distribution in ProCal
Eliminate cable sizing guesswork. ProCal balances voltage drop budgets across multi-tier distribution: from MV/LV transformer to main switchboard, sub-panels, and final circuit outlets.
Multi-Floor RisersIEC 61439-2 automated diversity across towers
Dynamic SLD GenerationInteractive Single Line Diagram with live breaker sync
1-Click ExportCompliant PDF & Excel calculation schedules